UPS and Inverter Size Calculator

The UPS or inverter size in VA and watts for your load, the nearest standard rating, and the current it draws from the battery.

W

Add up the watts of everything that will run together. Use the label or a plug-in power meter.

Watts = VA × power factor. 0.8 is a common figure for a UPS. If the maker rates the unit in watts at a power factor of 1, enter 1.

%

Spare capacity so the unit does not run at its limit. 25% is a common choice.

Motors draw several times their running watts for a moment. These multipliers are typical only, not exact.

%

Used for the battery side current only.

Recommended size

1.5 kVA

needs at least 1,250 VA, estimate

Connected load
800 W
Load in VA
1,000 VA
Watts needed with headroom
1,000 W
VA needed
1,250 VA
Real power of that size at this power factor
1,200 W
Battery side current at the connected load, 12 V
78.4 A
Battery side current at full rated power, 12 V
117.6 A

A load of 800 W needs about 1,250 VA with 25% headroom at power factor 0.8, so choose a 1.5 kVA unit.

Add this calculator to your website

Free to use on any site or blog. Paste this code where you want the calculator to appear. It stays up to date, needs no account, and keeps your visitors' numbers in their own browser.

Preview

How it works

A UPS or inverter has two ratings. Watts is the real power it can deliver. VA (volt-amps) is the total it can carry, and it is bigger because some loads, such as computers and motors, draw current that does not turn into useful power. The ratio is the power factor, and watts = VA × power factor.

Enter the load as one total, or list up to six devices with their quantity. The calculator adds headroom (25% by default) so the unit is not at its limit all day, then divides by the power factor to get the VA you need. It picks the next size up from a list of common ratings: 600, 800, 1000, 1500, 2000 and 3000 VA, then 5 and 10 kVA.

Motors need extra for a moment when they start. Choose a fridge, pump or air conditioner and enter its running watts. The tool multiplies those watts by a typical starting multiplier, then checks that the peak is inside what the unit can surge. Real motors vary a lot: a small fridge may start at 2 times, a deep well pump at 5 times or more. Use the figure on the label or from the maker when you have it.

The last rows give the current the inverter pulls from the battery at 12, 24 or 48 V. That decides the cable and fuse size on the battery side. The same load at 48 V draws a quarter of the current at 12 V.

Check it by hand: 800 W divided by a power factor of 0.8 is 1,000 VA. Add 25% headroom and you need 1,250 VA, so the next size up is 1.5 kVA. On the battery side, 800 W ÷ 0.85 efficiency ÷ 12 V = 78.4 A.

VA = watts ÷ power factor
Watts needed = connected watts × (1 + headroom)
Peak watts = other loads + motor watts × starting multiplier
Watts needed = the larger of the headroom figure and peak watts ÷ surge capability
DC current (A) = watts ÷ (inverter efficiency × battery volts)

Worked example

A load of 800 W, power factor 0.8, headroom 25%. Watts needed are 800 × 1.25 = 1,000 W. VA needed is 1,000 ÷ 0.8 = 1,250 VA. The next standard size is 1,500 VA, which delivers 1,200 W at a power factor of 0.8.

On a 12 V battery at 85% efficiency the 800 W load draws 800 ÷ (0.85 × 12) = 78.4 A. That is why a bigger system is usually 24 V or 48 V.

Good to know

  • The starting multipliers are typical values, not exact. A given fridge, pump or air conditioner can start at less or more than 3 times its running watts, and the surge an inverter allows is set by the maker. Check both on the nameplate or datasheet.
  • Many inverters are rated in watts and the VA figure is the same number or close to it. Others, like most UPS units, are rated in both. Always compare the watts rating of the product with the watts you need, not just the VA.
  • Long runtime with a UPS or inverter needs a battery bank sized separately. Use the battery backup calculator for that. The tool does not size cables or fuses. A licensed electrician should do the wiring for anything connected to a building.

Questions people ask

What size UPS do I need for my computer?

Add the watts of the computer, monitor and anything else on the UPS. Add 25% headroom and divide by 0.8 to get VA. A desktop PC at 300 W plus a monitor at 50 W is 350 W, so 350 × 1.25 ÷ 0.8 = 547 VA, which points to a 600 VA unit.

How do I convert VA to watts for a UPS?

Multiply VA by the power factor. A 1,000 VA UPS with a power factor of 0.8 gives 800 W. Some modern units are rated at 0.9 or 1, so read the watts rating on the box.

What size inverter do I need for a fridge?

Check the running watts on the label, often 100 to 200 W, and allow about 3 times that for starting. A fridge of 150 W starts at around 450 W, so a 1,000 VA inverter with 25% headroom covers it with spare room for a few lights. Use the motor option above for your own numbers.

What is the difference between VA and watts?

Watts is the real power used by the load. VA is the product of volts and amps. They are equal for a plain heater and differ for loads with a power factor below 1, like computer power supplies and motors.

Should I choose a 12 V, 24 V or 48 V inverter?

The bigger the load, the higher the voltage. As a rough guide, many small installers keep 12 V up to around 1,000 to 1,500 W, use 24 V up to about 3,000 W and 48 V above that. The reason is current: at 3,000 W, 12 V means over 280 A, which needs very thick cable.

What size UPS do I need for a 500 W load?

At power factor 0.8, 500 W is 625 VA. With 25% headroom you need at least 781 VA, so an 800 VA unit is the smallest that fits. On a 12 V battery the load draws about 49 A, allowing for 85% efficiency.

Part of the guide: Electrical, power and solar calculators: amps, wire size, generators and batteries