Add up the watts of everything that will run together. Use the label or a plug-in power meter.
Leave a device blank to skip it.
Blank counts as 1.
Watts = VA × power factor. 0.8 is a common figure for a UPS. If the maker rates the unit in watts at a power factor of 1, enter 1.
Spare capacity so the unit does not run at its limit. 25% is a common choice.
Motors draw several times their running watts for a moment. These multipliers are typical only, not exact.
It is part of the total above, not extra.
Many inverters allow about twice their rating for a few seconds, but it varies. Use the datasheet.
Used for the battery side current only.
Recommended size
1.5 kVA
needs at least 1,250 VA, estimate
A load of 800 W needs about 1,250 VA with 25% headroom at power factor 0.8, so choose a 1.5 kVA unit.
UPS and Inverter Size Calculator by Ivorytool, free tools that run in your browser.