UPS and Inverter Size Calculator

W

Add up the watts of everything that will run together. Use the label or a plug-in power meter.

Watts = VA × power factor. 0.8 is a common figure for a UPS. If the maker rates the unit in watts at a power factor of 1, enter 1.

%

Spare capacity so the unit does not run at its limit. 25% is a common choice.

Motors draw several times their running watts for a moment. These multipliers are typical only, not exact.

%

Used for the battery side current only.

Recommended size

1.5 kVA

needs at least 1,250 VA, estimate

Connected load
800 W
Load in VA
1,000 VA
Watts needed with headroom
1,000 W
VA needed
1,250 VA
Real power of that size at this power factor
1,200 W
Battery side current at the connected load, 12 V
78.4 A
Battery side current at full rated power, 12 V
117.6 A

A load of 800 W needs about 1,250 VA with 25% headroom at power factor 0.8, so choose a 1.5 kVA unit.

UPS and Inverter Size Calculator by Ivorytool, free tools that run in your browser.