How it works
A generator has to carry two things: the load that runs all the time, and the short surge when a motor starts. Add up the running watts of everything that will be on together. Then enter the running watts of the largest motor and pick its type. A motor draws several times its running watts for a second or two while it starts, so the calculator adds that extra on top of the running load to get the peak.
Typical starting multipliers are 1 for heaters and lights, about 3 for a fridge, freezer, pump or air conditioner and about 2.5 for a tool motor. These are typical figures, not exact. Your label or the maker's data is better.
kVA is kW divided by the power factor. Generator sets are normally rated at a power factor of 0.8, so a 10 kW generator is about 12.5 kVA. The calculator shows kW and kVA for the running and the starting load.
Generators lose output in thin air and heat. A common manufacturer rule of thumb is about 3.5% less per 1,000 ft above 500 ft. It is only a rule of thumb, and the derate chart from the maker of your generator is the figure to use. You can enter a temperature derate from that chart too.
The recommended size is the first standard rating at or above what you need. Because the starting rating of a generator is only a little above its running rating, the starting load is divided by the surge ratio you enter (1.2 by default) before the comparison.
Check it by hand: the rated size is the highest load the generator must carry, divided by the surge allowance. A peak of 5 kW divided by 1.2 is 4.17 kW, so the next common size up, 5 kW, is the answer. The running load of 3 kW then uses 60% of that rating.
Peak watts = running watts + motor watts × (starting multiplier − 1) kVA = kW ÷ power factor (generator sets are rated at 0.8) Altitude derate (%) = 3.5 × (feet − 500) ÷ 1,000, a rule of thumb Rated kW needed = the larger of running kW and peak kW ÷ surge ratio, then ÷ (1 − altitude derate) ÷ (1 − temperature derate) Fuel (L) = litres per hour at load × hours
Worked example
Appliances running together total 3,000 W, including a 1,000 W pump with a typical 3x start. Peak is 3,000 + 1,000 × 2 = 5,000 W. Running load is 3.00 kW or 3.75 kVA at 0.8. The peak is 5.00 kW or 6.25 kVA.
With a surge ratio of 1.2, the peak gives 5.00 ÷ 1.2 = 4.17 kW, which is above the running 3.00 kW. The next standard size is 5 kW. At 5,000 ft the altitude derate is 3.5 × 4.5 = 15.75%, so the rated size needed rises to 4.95 kW, which is still a 5 kW unit but with almost no margin.
Good to know
- This is an estimate. The surge a real generator can give, and the motor start it can handle without the voltage dropping too far, depend on the model. Use the starting watts on its datasheet. Motors started one after another need less than motors started together, so start the biggest first.
- The 3.5% per 1,000 ft altitude figure is a common rule of thumb. Some makers give a different rate for petrol, diesel and inverter models, and temperature derates vary a lot. The derate chart from your generator's maker always wins.
- Electronics such as computers and some medical devices need clean power, which usually means an inverter generator. Connecting a generator to a home needs a proper transfer switch fitted by a licensed electrician. Never run a generator indoors or in a garage, since carbon monoxide kills.
- The fuel estimate multiplies the litres per hour you enter. The tool does not guess fuel use, because it changes with the load share, the engine and the fuel.
Questions people ask
What size generator do I need for my house?
Add up the running watts of what you want on during an outage (fridge, lights, fans, router, a few outlets), then add the extra starting watts of the largest motor. A basic essentials setup is often 3 to 5 kW. A whole house with central air conditioning and an electric range or heater can need 15 to 20 kW or more.
What is the difference between running watts and starting watts?
Running watts is what an appliance uses once it is going. Starting (surge) watts is the short peak, mostly for motors, when they start. A fridge that runs at 150 W may need 450 W or more to start. Size the generator for the running total plus the extra of the biggest start.
How many kVA is a 10 kW generator?
At the usual power factor of 0.8, a 10 kW generator is 12.5 kVA. A 20 kW generator is 25 kVA. A 7.5 kW generator is about 9.4 kVA. Divide kW by 0.8.
Does altitude affect a generator?
Yes. Thinner air gives an engine less power. A common rule of thumb is about 3.5% less per 1,000 ft above 500 ft, so a generator at 5,000 ft gives roughly 84% of its sea level rating. Check the maker's chart for the real figure.
How much fuel does a generator use?
It depends on the engine and the load. Look up the litres per hour at your load on the maker's data sheet or measure it, then enter it in the fuel box. Fuel for the run is litres per hour times the hours.
Should I add a safety margin to the generator size?
Running a generator near its limit all day wears it out. Aim for the running load to be no more than about 80% of the rating. The tool shows the share of the rating the running load uses, so you can check.
What size generator do I need for a 3 kW load with a water pump?
With a 3 kW running load and a 1 kW pump motor, the calculator suggests a 5 kW generator. The peak while the pump starts is 5 kW, and with the 1.2 allowance for the generator’s own surge rating it needs at least 4.17 kW rated. Add your own appliances to see the change.
Part of the guide: Electrical, power and solar calculators: amps, wire size, generators and batteries