Electrical Load Calculator

The connected and demand load of a home or small building from a list of appliances, with kVA, current, and daily and monthly kWh.

W

Watts of one unit, from its label. Leave a line blank to skip it.

Blank counts as 1.

h

Average hours of actual running per day. Blank counts as 0 for the energy.

W

h

W

h

W

h

W

h

W

h

W

h

W

h

W

h

W

h

The share of the connected load likely to be on at once, from 0.1 to 1. 0.7 is a planning guess. For a real installation, demand factors are set by your local electrical code.

1 for heaters and lights, about 0.8 to 0.9 for a mixed home with motors and electronics.

For three phase this is the line to line voltage and the load is assumed to be balanced.

Demand load

2.64 kW

planning estimate, connected load 3.77 kW

Connected load
3,770 W (3.77 kW)
Demand load
2,639 W (2.64 kW)
Demand load in kVA
2.93 kVA
Current at demand load, 230 V single phase
12.7 A
Current if everything is on at once
18.2 A
Energy per day
29.8 kWh
Energy per month (30 days)
894 kWh

Your 3,770 W of connected load becomes about 2.64 kW of demand with a factor of 0.7, which is 12.7 A at 230 V single phase, and you use about 29.8 kWh a day.

Add this calculator to your website

Free to use on any site or blog. Paste this code where you want the calculator to appear. It stays up to date, needs no account, and keeps your visitors' numbers in their own browser.

Preview

How it works

List your appliances, up to ten lines. For each line give the watts of one unit, how many there are, and the hours per day it actually runs. The calculator adds watts times quantity to get the connected load, which is the total if everything were on at once.

In a real building, not everything runs at once. A demand factor takes that into account. 0.7 means you expect 70% of the connected load to be on at the busiest time. The result is the demand load. Change the factor to suit your case. A house with a lot of air conditioning may need a higher number than one with a few lights and a fridge.

The demand load in watts is then divided by the power factor to get kVA, and the kVA gives the current: divide by the voltage for single phase, or by 1.732 times the voltage for three phase. This is the number you compare with a breaker, a generator, an inverter or a supply rating.

Daily energy is watts times quantity times hours, divided by 1,000, added over all lines. Monthly energy multiplies that by 30 days. These use your hours as entered, and the demand factor is not applied to energy. For lighting, enter the number of lamps and the watts of each lamp, since lighting load is simply lamps times watts.

Check it by hand: energy is watts × quantity × hours. The five default lines use 10 × 12 × 5 = 600 Wh, 150 × 8 = 1,200 Wh, 1,500 × 2 × 8 = 24,000 Wh, 75 × 4 × 10 = 3,000 Wh and 100 × 2 × 5 = 1,000 Wh, a total of 29,800 Wh, or 29.8 kWh a day. The connected load is 120 + 150 + 3,000 + 300 + 200 = 3,770 W. At a 0.7 demand factor the demand load is 3,770 × 0.7 = 2,639 W. At power factor 0.9 that is 2.639 ÷ 0.9 = 2.93 kVA, and on 230 V the current is 2,639 ÷ (230 × 0.9) = 12.7 A.

Connected load (W) = sum of watts × quantity
Demand load (W) = connected load × demand factor
kVA = demand load ÷ (1,000 × power factor)
Current, single phase (A) = kVA × 1,000 ÷ volts
Current, three phase (A) = kVA × 1,000 ÷ (1.732 × line voltage)
Energy per day (kWh) = sum of watts × quantity × hours ÷ 1,000

Worked example

The default list is 12 lamps of 10 W for 5 hours, a 150 W fridge for 8 hours, two 1,500 W air conditioners for 8 hours, four 75 W fans for 10 hours and two 100 W TVs for 5 hours. Connected load is 120 + 150 + 3,000 + 300 + 200 = 3,770 W.

With a demand factor of 0.7 the demand load is 2,639 W. At a power factor of 0.9 that is 2.93 kVA, and 12.7 A on a 230 V single-phase supply. Energy is 0.6 + 1.2 + 24 + 3 + 1 = 29.8 kWh a day, or 894 kWh over 30 days.

Good to know

  • This is a planning estimate, not a code-compliant load calculation. Service and feeder calculations for a real installation, such as those under NEC Article 220 in the United States, use specific rules for lighting per square metre or foot, appliance and range demand factors, and the largest motor, and they must be done by a licensed electrician. The demand factor here is a number you choose, not a code value.
  • Watts on a label are often the maximum. Fridges, pumps and air conditioners cycle on and off, so their average is lower than the label but their starting current is higher. Measure with a plug-in meter for better energy figures.
  • The tool assumes three-phase loads are balanced across the phases. It does not size wires or breakers. Use the wire size calculator for cable and ask an electrician about protection.

Questions people ask

How do I calculate my electrical load?

List each appliance with its watts and quantity and add them. That is the connected load. Multiply by a demand factor for the share likely to run together to get the demand load, then divide by the voltage to get amps. This tool does those steps for up to ten lines.

How do I calculate lighting load?

Multiply the number of lamps by the watts of each lamp. Forty LED lamps of 9 W is 360 W. Enter it as one line with quantity 40. For a building, local code usually sets a minimum lighting load per square metre or foot of floor area, so check your code for the figure to use.

What is a demand factor?

It is the ratio of the load you expect at the busiest moment to the total connected load. It is below 1 because not everything runs at once. A real service calculation takes the factors from the local electrical code, so treat 0.7 here as a rough planning figure.

How do I estimate my electricity usage?

For each appliance multiply watts by hours per day and divide by 1,000 to get kWh a day. Add them up and multiply by 30 for a month. The calculator does this and shows both numbers. A plug-in power meter gives better figures than label watts.

How many amps is my load?

Divide the load in VA by the voltage. For example 5,000 VA at 230 V single phase is 21.7 A. On a 400 V three-phase supply it is 5,000 ÷ (1.732 × 400) = 7.2 A per phase. Pick the supply above to get the figure for your demand load.

What is the current if all 3,770 W are on at once on a 230 V supply?

3,770 ÷ (230 × 0.9) = 18.2 A, using a power factor of 0.9.