100 kVA in kW at common power factors
| Power factor | kW |
|---|---|
| 0.7 | 70 |
| 0.8 | 80 |
| 0.85 | 85 |
| 0.9 | 90 |
| 0.95 | 95 |
| 1 | 100 |
kVA to kW or kW to kVA from the power factor, with kVAR, the phase angle and the line current in amps.
| Power factor | kW |
|---|---|
| 0.7 | 70 |
| 0.8 | 80 |
| 0.85 | 85 |
| 0.9 | 90 |
| 0.95 | 95 |
| 1 | 100 |
kVA is apparent power, the voltage times the current. kW is real power, the part that does the work. They differ by the power factor: kW = kVA × power factor. So a 100 kVA generator rated at a power factor of 0.8 can supply 80 kW, and a load of 80 kW at 0.8 needs 100 kVA.
The rest is a right triangle. Real power (kW) and reactive power (kVAR) are the two sides and apparent power (kVA) is the long side. The angle between kW and kVA has a cosine equal to the power factor. The calculator returns kVAR and the angle too.
Enter a voltage to get the current. For single phase, amps = kVA × 1000 ÷ volts. For three phase with the voltage between two lines, amps = kVA × 1000 ÷ (1.732 × volts). Both are shown, so use the row that matches your supply. The table lists the same value at the usual power factors.
Check it by hand: real power = apparent power × power factor, so 100 kVA × 0.8 = 80 kW. Reactive power is √(100² − 80²) = √3,600 = 60 kVAR, and the phase angle is the arccos of 0.8, which is 36.87 degrees. The three-phase current at 400 V is 100,000 ÷ (1.732 × 400) = 144.3 A, and single phase is 100,000 ÷ 400 = 250 A.
kW = kVA × PF kVA = kW ÷ PF kVAR = √(kVA² − kW²) = kVA × sin(φ) φ = arccos(PF) Single phase: A = kVA × 1000 ÷ V Three phase: A = kVA × 1000 ÷ (1.732 × V line to line) Source: the standard power triangle (IEEE Std 1459 defines active, reactive and apparent power).
A generator rated at 100 kVA with a power factor of 0.8 delivers 100 × 0.8 = 80 kW. The reactive power is √(100² − 80²) = 60 kVAR and the phase angle is arccos(0.8) = 36.87 degrees.
On a 400 V three-phase supply the full-load current is 100,000 ÷ (1.732 × 400) = 144.3 A.
Multiply kVA by the power factor. At a power factor of 0.8, 100 kVA is 80 kW. At 0.9 it is 90 kW and at 1 it is 100 kW.
Divide kW by the power factor. 80 kW at a power factor of 0.8 is 100 kVA. At 0.9, 80 kW is 88.9 kVA.
kW is the real power that turns a motor or heats an element. kVA is the total power the supply has to carry, which includes reactive power that does no work. kVA is always equal to or larger than kW.
Generators are normally rated at 0.8, which is the default here. If you know the actual load, such as lights and heaters at near 1 or motors at 0.8 to 0.9, use that.
1 kVA is 1000 volt-amps. At a power factor of 0.8 that is 800 W, and at a power factor of 1 it is 1000 W.
kVAR is reactive power, the part of the supply current that builds the magnetic fields of motors and transformers and does no work. kVA² = kW² + kVAR².
Enter the voltage in the calculator. For three phase, amps = kVA × 1000 ÷ (1.732 × line voltage). For single phase, amps = kVA × 1000 ÷ voltage.
80 kW. Multiply 100 by 0.8. At a power factor of 1.0 it would be 100 kW.