Catalogue output (delta T 50) needed for different water temperatures
| Delta T | Example flow/return in a 20 °C room | Factor | Output needed at delta T 50 |
|---|---|---|---|
| 30 | 55/45 °C | 0.515 | 3,264 W |
| 40 | 65/55 °C | 0.748 | 2,245 W |
| 50 | 75/65 °C | 1 | 1,680 W |
The watts and BTU per hour a room needs from its size, walls and windows, and the radiator output to choose for your water temperature.
| Delta T | Example flow/return in a 20 °C room | Factor | Output needed at delta T 50 |
|---|---|---|---|
| 30 | 55/45 °C | 0.515 | 3,264 W |
| 40 | 65/55 °C | 0.748 | 2,245 W |
| 50 | 75/65 °C | 1 | 1,680 W |
A radiator must give the room as much heat as it loses on the coldest day. The calculator uses the common rule-of-thumb method used in UK and European radiator guides: take the room volume, multiply by a base figure of 50 watts per cubic metre (about 5 BTU per cubic foot), then adjust it for the number of external walls, the glazing, what is above and below the room, and the temperature difference between the room and the outside.
Radiators are sold with an output at delta T 50, which means the average water temperature is 50 °C above the room. That is the standard rating of BS EN 442, for example 75 °C flow and 65 °C return in a 20 °C room. If your water is cooler, the radiator gives less. The output at another delta T is output at delta T 50 × (delta T ÷ 50)^1.3, where 1.3 is the typical radiator exponent in the EN 442 test method. At delta T 30 the factor is 0.515, so the radiator gives about half its catalogue output.
Delta T is the mean water temperature, which is the average of flow and return, minus the room temperature. The result gives the output to look for in the catalogue at delta T 50. If you have a heat pump or a condensing boiler with low flow temperatures, a radiator must be much bigger than for a traditional boiler.
Check it by hand: a room of 4 × 3.5 × 2.4 m has a volume of 33.6 m³. With the default room settings the heat it needs comes to 50 W per m³, so 33.6 × 50 = 1,680 W. Water at 75 °C flow and 65 °C return has a mean of 70 °C, and with a room at 21 °C the delta T is 49 °C. Radiators are rated at delta T 50, so the output factor is (49 ÷ 50)^1.3 = 0.974. The catalogue output needed is 1,680 ÷ 0.974 = 1,725 W.
Room watts = volume (m³) × 50 W/m³ × wall factor × glazing factor × ceiling factor × floor factor × (room − outside °C) ÷ 24 BTU/h = watts × 3.412 Delta T = (flow + return) ÷ 2 − room temperature Output at delta T = output at delta T 50 × (delta T ÷ 50)^1.3 (BS EN 442) Output needed at delta T 50 = room watts ÷ (delta T ÷ 50)^1.3
A room of 4 m × 3.5 m with a 2.4 m ceiling is 33.6 m³. It has one external wall, double glazing, an insulated loft above and a ground floor below, with 21 °C inside and -3 °C outside (a difference of 24 K, so no change to the base figure). Heat needed = 33.6 × 50 = 1,680 W, which is 5,732 BTU per hour.
The boiler runs at 75 °C flow and 65 °C return, so the mean water is 70 °C, 49 K above the room. The factor is (49 ÷ 50)^1.3 = 0.974. The radiator must be rated at 1,680 ÷ 0.974 = 1,725 W at delta T 50. If the flow drops to 55 °C and the return to 45 °C, delta T is 29 and the factor 0.493, so the rating needed at delta T 50 becomes about 3,400 W.
Find the room volume, multiply by about 50 watts per cubic metre, then adjust for external walls, windows and the floors and ceilings around the room. A typical 33.6 m³ room with one external wall needs about 1,680 W, or 5,732 BTU per hour.
Radiators are sized by room volume rather than floor area. About 5 BTU per cubic foot of room is the usual base figure, which is 50 W per cubic metre, before adjusting for walls, windows and temperature.
It is the standard test condition: the average water temperature is 50 °C above the room, for example 75 °C flow and 65 °C return in a 20 °C room. Catalogue outputs are quoted at this condition.
Output = output at delta T 50 × (delta T ÷ 50)^1.3. At delta T 30 it gives 0.515 of the catalogue output, at delta T 40 it gives 0.748.
Usually yes. A heat pump runs the water at a lower temperature, so each radiator gives less. At delta T 30, about half the catalogue output, you need about double the rated output or more radiator surface.
Catalogue outputs are given at delta T 50. A lower water temperature gives a smaller delta T, and output falls with delta T raised to the power 1.3, so you need a bigger radiator.
Part of the guide: Heating, cooling and water calculators: BTU, pipes, tanks, pumps and pools