Radiator Size Calculator

The watts and BTU per hour a room needs from its size, walls and windows, and the radiator output to choose for your water temperature.

m

m

m

°C

21 °C for living rooms and 18 °C for bedrooms are common design values.

°C

The design temperature for your area. The factors below are set for 21 °C inside and -3 °C outside.

°C

A traditional boiler runs at about 75 °C. A heat pump or condensing boiler run at 45 to 55 °C.

°C

Usually 10 °C (20 °F) below the flow temperature for a boiler, and 5 °C for a heat pump.

Radiator output needed at delta T 50

1,725 W

5,885 BTU per hour at delta T 50. The room itself needs 1,680 W.

Room volume
33.6 m³ (1,187 cu ft)
Heat the room needs
1,680 W (5,732 BTU per hour)
Mean water temperature minus room (delta T)
49 °C
Output compared with delta T 50
0.974 × the catalogue output
Catalogue output needed at delta T 50
1,725 W (5,885 BTU per hour)

A room of 33.6 m³ loses about 1,680 W on a design day. With water at a mean 49 °C above the room, pick a radiator rated at least 1,725 W at delta T 50.

Add this calculator to your website

Free to use on any site or blog. Paste this code where you want the calculator to appear. It stays up to date, needs no account, and keeps your visitors' numbers in their own browser.

Preview

Catalogue output (delta T 50) needed for different water temperatures

Catalogue output (delta T 50) needed for different water temperatures
Delta TExample flow/return in a 20 °C roomFactorOutput needed at delta T 50
3055/45 °C0.5153,264 W
4065/55 °C0.7482,245 W
5075/65 °C11,680 W

How it works

A radiator must give the room as much heat as it loses on the coldest day. The calculator uses the common rule-of-thumb method used in UK and European radiator guides: take the room volume, multiply by a base figure of 50 watts per cubic metre (about 5 BTU per cubic foot), then adjust it for the number of external walls, the glazing, what is above and below the room, and the temperature difference between the room and the outside.

Radiators are sold with an output at delta T 50, which means the average water temperature is 50 °C above the room. That is the standard rating of BS EN 442, for example 75 °C flow and 65 °C return in a 20 °C room. If your water is cooler, the radiator gives less. The output at another delta T is output at delta T 50 × (delta T ÷ 50)^1.3, where 1.3 is the typical radiator exponent in the EN 442 test method. At delta T 30 the factor is 0.515, so the radiator gives about half its catalogue output.

Delta T is the mean water temperature, which is the average of flow and return, minus the room temperature. The result gives the output to look for in the catalogue at delta T 50. If you have a heat pump or a condensing boiler with low flow temperatures, a radiator must be much bigger than for a traditional boiler.

Check it by hand: a room of 4 × 3.5 × 2.4 m has a volume of 33.6 m³. With the default room settings the heat it needs comes to 50 W per m³, so 33.6 × 50 = 1,680 W. Water at 75 °C flow and 65 °C return has a mean of 70 °C, and with a room at 21 °C the delta T is 49 °C. Radiators are rated at delta T 50, so the output factor is (49 ÷ 50)^1.3 = 0.974. The catalogue output needed is 1,680 ÷ 0.974 = 1,725 W.

Room watts = volume (m³) × 50 W/m³ × wall factor × glazing factor × ceiling factor × floor factor × (room − outside °C) ÷ 24
BTU/h = watts × 3.412
Delta T = (flow + return) ÷ 2 − room temperature
Output at delta T = output at delta T 50 × (delta T ÷ 50)^1.3   (BS EN 442)
Output needed at delta T 50 = room watts ÷ (delta T ÷ 50)^1.3

Worked example

A room of 4 m × 3.5 m with a 2.4 m ceiling is 33.6 m³. It has one external wall, double glazing, an insulated loft above and a ground floor below, with 21 °C inside and -3 °C outside (a difference of 24 K, so no change to the base figure). Heat needed = 33.6 × 50 = 1,680 W, which is 5,732 BTU per hour.

The boiler runs at 75 °C flow and 65 °C return, so the mean water is 70 °C, 49 K above the room. The factor is (49 ÷ 50)^1.3 = 0.974. The radiator must be rated at 1,680 ÷ 0.974 = 1,725 W at delta T 50. If the flow drops to 55 °C and the return to 45 °C, delta T is 29 and the factor 0.493, so the rating needed at delta T 50 becomes about 3,400 W.

Good to know

  • The wall, glazing, floor and ceiling factors are typical rule-of-thumb steps, not measured values. This is an estimate for choosing a radiator. For a whole system or a heat pump, a room-by-room heat loss calculation to BS EN 12831 (or the equivalent in your country) is the right method.
  • Rooms with unusually large windows, poor draught proofing, a conservatory, or very high ceilings can lose much more. Bathrooms are usually designed for a higher temperature, such as 22 °C.
  • Radiator makers publish the output at delta T 50 in their catalogue, and many publish delta T 30 and 40 as well. Use their figures where they exist. Some types have a slightly different exponent.
  • Add a margin only if the manufacturer's output is the minimum you can accept. Oversized radiators suit low-temperature systems, and an undersized one never heats the room.

Questions people ask

How do I work out what size radiator I need for a room?

Find the room volume, multiply by about 50 watts per cubic metre, then adjust for external walls, windows and the floors and ceilings around the room. A typical 33.6 m³ room with one external wall needs about 1,680 W, or 5,732 BTU per hour.

How many BTU do I need per square foot for a radiator?

Radiators are sized by room volume rather than floor area. About 5 BTU per cubic foot of room is the usual base figure, which is 50 W per cubic metre, before adjusting for walls, windows and temperature.

What is delta T 50 on a radiator?

It is the standard test condition: the average water temperature is 50 °C above the room, for example 75 °C flow and 65 °C return in a 20 °C room. Catalogue outputs are quoted at this condition.

How much less heat does a radiator give at a lower flow temperature?

Output = output at delta T 50 × (delta T ÷ 50)^1.3. At delta T 30 it gives 0.515 of the catalogue output, at delta T 40 it gives 0.748.

Do I need bigger radiators for a heat pump?

Usually yes. A heat pump runs the water at a lower temperature, so each radiator gives less. At delta T 30, about half the catalogue output, you need about double the rated output or more radiator surface.

Why does a radiator give less than its catalogue output on a cooler boiler setting?

Catalogue outputs are given at delta T 50. A lower water temperature gives a smaller delta T, and output falls with delta T raised to the power 1.3, so you need a bigger radiator.

Part of the guide: Heating, cooling and water calculators: BTU, pipes, tanks, pumps and pools

Formulas and text last checked on 7 October 2026. Everything is calculated in your browser, so nothing you enter is sent or stored. Spotted a mistake? Tell us and we will fix it.