Radiator Size Calculator

m

m

m

°C

21 °C for living rooms and 18 °C for bedrooms are common design values.

°C

The design temperature for your area. The factors below are set for 21 °C inside and -3 °C outside.

°C

A traditional boiler runs at about 75 °C. A heat pump or condensing boiler run at 45 to 55 °C.

°C

Usually 10 °C (20 °F) below the flow temperature for a boiler, and 5 °C for a heat pump.

Radiator output needed at delta T 50

1,725 W

5,885 BTU per hour at delta T 50. The room itself needs 1,680 W.

Room volume
33.6 m³ (1,187 cu ft)
Heat the room needs
1,680 W (5,732 BTU per hour)
Mean water temperature minus room (delta T)
49 °C
Output compared with delta T 50
0.974 × the catalogue output
Catalogue output needed at delta T 50
1,725 W (5,885 BTU per hour)

A room of 33.6 m³ loses about 1,680 W on a design day. With water at a mean 49 °C above the room, pick a radiator rated at least 1,725 W at delta T 50.

Radiator Size Calculator by Ivorytool, free tools that run in your browser.