21 °C for living rooms and 18 °C for bedrooms are common design values.
The design temperature for your area. The factors below are set for 21 °C inside and -3 °C outside.
A traditional boiler runs at about 75 °C. A heat pump or condensing boiler run at 45 to 55 °C.
Usually 10 °C (20 °F) below the flow temperature for a boiler, and 5 °C for a heat pump.
Radiator output needed at delta T 50
1,725 W
5,885 BTU per hour at delta T 50. The room itself needs 1,680 W.
A room of 33.6 m³ loses about 1,680 W on a design day. With water at a mean 49 °C above the room, pick a radiator rated at least 1,725 W at delta T 50.