Duct Size Calculator

The round duct diameter for an airflow, by friction rate or velocity, with the equivalent rectangular duct and the actual air velocity.

The airflow the duct must carry, in the unit chosen next.

in wg per 100 ft

0.08 to 0.10 is a common design value for home duct systems.

in

Pick a width to get the matching height with the same friction. Blank to skip.

Round duct diameter

11 in

calculated 10.3 in (261 mm), velocity 606 fpm (3.1 m/s)

Airflow
400 cfm, 188.8 L/s, 680 m³/h
Calculated round diameter
10.3 in (261 mm)
Standard size at or above
11 in (279 mm)
Actual velocity in that size
606 fpm (3.08 m/s)
Friction loss in that size
0.057 in wg per 100 ft (0.46 Pa/m)
Rectangular duct height for equal friction
7.5 in high, for a width of 12 in
Rounded up to a whole size
12 in × 8 in, equivalent to a 10.7 in (271 mm) round duct
Shape
Aspect ratio 1.5:1, within 4:1

400 cfm in a round duct needs a diameter of 11 in, which gives an air velocity of 606 fpm.

Add this calculator to your website

Free to use on any site or blog. Paste this code where you want the calculator to appear. It stays up to date, needs no account, and keeps your visitors' numbers in their own browser.

Preview

How it works

Air in a duct loses pressure to friction on the walls. A narrow duct is cheap but loud and wastes fan power, and a wide one is quiet but takes space. Duct designers pick a size either by a friction rate (the pressure lost per 100 feet of duct) or by an air velocity.

By friction rate the calculator turns the standard round duct friction equation around, solving it for the diameter. In imperial units the friction loss is Δp = 0.109136 × Q^1.9 ÷ D^5.02, in inches of water gauge per 100 feet, with Q in CFM and D in inches. This is the form used in the ASHRAE duct design charts and printed by Engineering Toolbox for clean galvanised round duct. By velocity it uses the plain area relation, diameter = √(4 × Q ÷ (π × velocity)).

Round duct comes in whole inches (or the standard metric sizes), so the calculator rounds up to the next size and then shows the real velocity and friction in that size. A rectangular duct with the same friction as a round one is given by the equal-friction equivalent diameter, De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25, where a and b are the sides in the same unit. Enter a width and the calculator finds the height whose De matches the round duct.

To get the airflow for each room, split the system airflow by each room's share of the heating or cooling load. A common rule of thumb is about 400 CFM per ton of cooling, so a 3 ton system moves about 1,200 CFM. Run the tool once per branch and for the main trunk.

Check it by hand: for 400 cfm at a friction rate of 0.08 in wg per 100 ft the calculated round duct is 10.3 in, so you round up to the standard 11 in. The area of an 11 in round duct is 3.1416 × (11 ÷ 12)² ÷ 4 = 0.66 sq ft. The air speed is then 400 ÷ 0.66 = 606 feet per minute, which is the velocity the tool reports.

Δp (in wg per 100 ft) = 0.109136 × Q^1.9 ÷ D^5.02     (Q in CFM, D in inches, round duct)
D = (0.109136 × Q^1.9 ÷ Δp)^(1 ÷ 5.02)
By velocity: D (in) = 12 × √(4 × Q ÷ (π × V))     (V in fpm)
Equivalent round for a × b: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25
Conversions: 1 L/s = 2.119 CFM, 1 m³/h = 0.5886 CFM, 1 in wg per 100 ft = 8.172 Pa/m

Worked example

400 CFM at a friction rate of 0.08 in wg per 100 ft. D = (0.109136 × 400^1.9 ÷ 0.08)^(1 ÷ 5.02) = 10.27 in. The next standard size is 11 in.

In the 11 in duct the velocity is 606 fpm (400 ÷ 0.660 sq ft) and the friction falls to 0.057 in wg per 100 ft. For a rectangular duct 12 in wide, the equal-friction height is 7.46 in, so use 12 × 8 in, which is equivalent to a 10.7 in round duct and has an aspect ratio of 1.5:1.

Good to know

  • The equation is for clean, round, galvanised steel duct with standard air at sea level. Flexible duct, fibreglass duct board, rough surfaces, altitude and temperature change the friction. Flexible duct loses much more pressure for the same size, so size it up and keep it short and straight.
  • The result covers straight runs. Elbows, tees, dampers, registers, filters and coils add their own pressure drop. The fan must overcome the total, which a full duct design (for example from ACCA Manual D) works out.
  • The rectangular size is equal in friction, not in area or velocity. The air speed in a rectangular duct is not the same as in the round duct of equal friction.
  • This is a sizing aid. Check the result against your local code and the equipment maker's data.

Questions people ask

What round duct size do I need for 100, 200, 400, 600, 800 or 1,000 CFM?

At a friction rate of 0.08 inches of water per 100 feet, the calculated round duct diameters are about 6.1 in for 100 CFM, 7.9 in for 200 CFM, 10.3 in for 400 CFM, 12.0 in for 600 CFM, 13.4 in for 800 CFM and 14.5 in for 1,000 CFM. Round up to the next stock size, and use the calculator for your own friction rate.

What size duct do I need for 400 CFM?

At a friction rate of 0.08 in wg per 100 ft a round duct of 10.3 in is needed, so use an 11 in duct, which carries 400 CFM at 606 fpm.

How do I convert CFM to duct size?

Pick a friction rate or a velocity, then solve for the diameter. By velocity, diameter = 12 × √(4 × CFM ÷ (π × fpm)), so 400 CFM at 700 fpm needs about 10.2 in.

What register size do I need for a given CFM?

Register sizes come from the maker's chart, which depends on the throw and the noise limit. As a check, the neck area is CFM ÷ face velocity. For 400 CFM at 500 fpm that is 0.8 sq ft (115 sq in).

How do I calculate CFM per room?

Share the system airflow in proportion to each room's heating or cooling load, which is best taken from a Manual J load calculation. Then size each branch with the CFM for that room. This tool sizes the duct once you have the CFM.

How do I convert a round duct to a rectangular one?

Use the equal-friction equation De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Enter a width and the calculator finds the height. A 12 × 8 in duct is equivalent to a 10.7 in round duct.

Why is the duct rounded up to a standard size?

Duct is sold in standard sizes. Rounding up keeps the friction and velocity at or below the values you chose.

Part of the guide: Heating, cooling and water calculators: BTU, pipes, tanks, pumps and pools

Formulas and text last checked on 7 October 2026. Everything is calculated in your browser, so nothing you enter is sent or stored. Spotted a mistake? Tell us and we will fix it.