How it works
A wire must satisfy two limits. It has to carry the current without overheating, and it has to keep the voltage drop small so that the load still gets close to its rated voltage. The calculator checks both and gives the smaller wire that meets both.
For the current limit, it uses the ampacity table of the US National Electrical Code (NEC Table 310.16) for the insulation rating you pick, with the usual caps on the smallest sizes (15 A for 14 AWG copper, 20 A for 12 AWG and 30 A for 10 AWG). For a load that runs three hours or more, it adds 25%.
For the voltage drop, the loss is the current times the resistance of the wire. A single-phase or DC circuit has the current going out and coming back, so it counts twice the length. Three-phase counts 1.732 times the length. The resistance uses copper or aluminium at 75 °C, which is a little higher than at room temperature, so the result is on the safe side. The minimum area is the current times the length times these factors, divided by the allowed drop in volts.
The result is shown as an AWG size and as the next standard metric size in square millimetres, so the answer works for American, Pakistani, Indian and European cable catalogues. The second tab converts a gauge to its area and diameter, and a metric area to the nearest gauge.
Check it by hand: the voltage allowed to drop at 230 V with a 3% limit is 6.9 V. A longer run or a higher current needs a thicker wire to stay inside it. For 30 A over 30 m, 5.46 mm² is the smallest copper size that fits, so the next standard size, 6 mm², is the answer. It then loses 6.28 V, or 2.73%.
Current = watts ÷ volts (single phase) or watts ÷ (1.732 × volts) (three phase) Minimum area (mm²) = k × ρ × current × one-way length (m) ÷ allowed drop (V) k = 2 (single phase or DC) or 1.732 (three phase) ρ at 75 °C: copper 0.0209, aluminium 0.0345 ohm·mm²/m AWG diameter (mm) = 0.127 × 92^((36 − n) ÷ 39)
Worked example
A 30 amp load at 230 V, 30 metres from the supply, with a 3% drop allowed (6.9 V). The voltage drop alone needs 2 × 0.0209 × 30 × 30 ÷ 6.9 = 5.46 mm².
For the current, 30 A needs at least 10 AWG (5.26 mm²) in copper at 75 °C. That is a little too small for the drop, so the calculator picks 8 AWG (8.37 mm²). The next standard metric size at or above 5.46 mm² is 6 mm².
Good to know
- The current ratings come from the US NEC for wire in conduit at 30 °C with three or fewer current-carrying conductors. Other codes, such as BS 7671 or the Pakistani and Indian rules, give different ratings for cables in air, clipped to a wall, buried or in bundles. A metric size here is the next standard size at or above the AWG result, so check it against your local code and the cable maker's table.
- Hot places, many cables in one conduit and long runs in direct sun need a larger wire. Apply the derating your code gives.
- Motor starting current, short-circuit rating, cable bends and joints are not covered. This is a first estimate. A licensed electrician must confirm the design, particularly for panels, solar arrays, and anything above 100 amps.
- Above 4/0 AWG (about 230 amps in copper) the calculator stops, since larger cables need parallel runs and a proper design.
Questions people ask
What wire size do I need for 30 amps?
In the US, 10 AWG copper carries 30 amps at 75 °C. On a long run, voltage drop may need a larger size. Enter your length and voltage in the calculator for the size, in AWG and in mm², and check it against your local code.
How do I calculate voltage drop in a cable?
Multiply the current by the resistance of the cable, and count the length out and back. For single phase, drop = 2 × resistivity × current × one-way length ÷ area. Compare the result with 3% of the supply voltage.
What is 10 AWG in mm²?
10 AWG has a cross-section of 5.26 mm² and a diameter of 2.59 mm. The nearest standard metric sizes are 4 mm² and 6 mm².
Can I use aluminium wire instead of copper?
Yes, but it needs about 1.6 times the area for the same resistance and has lower ampacity. Use connectors rated for aluminium. Switch the conductor to Aluminium and the calculator takes this into account.
What voltage drop is acceptable?
Most codes suggest no more than 3% on a branch circuit and 5% from the supply to the farthest load. Lower is better for motors and electronics.
What wire size do I need for 30 amps over 30 metres?
For single-phase copper at 230 V with a 3% voltage drop limit, the calculator gives 6 mm² (about 8 AWG), with a drop of 2.73%. The smallest size by voltage drop alone is 5.46 mm². Local wiring rules and the cable type can change the result, so check them before you buy.
Part of the guide: Electrical, power and solar calculators: amps, wire size, generators and batteries