Wire Size Calculator

Wire size

V

For three phase, the voltage between two lines, for example 400.

Watts and kilowatts assume a power factor of 1. For motors, use the amps on the label.

m

From the supply to the load, not there and back.

%

3% is the usual limit for a branch circuit and 5% for the whole run.

The lowest rating of the wire, the breaker and the terminals. 75 °C suits most installations.

Wire or cable size

6 mm²

or 8 AWG

Current
30 A
Smallest size for the voltage drop
5.46 mm²
Smallest size for the current (AWG)
10 AWG, 30 A
Size in AWG
8 AWG (8.37 mm²)
Size in square millimetres
6 mm²
Current rating of the AWG size
50 A
Voltage drop with the AWG size
4.5 V (1.96%)
Voltage drop with the mm² size
6.28 V (2.73%)

A load of 30 A over 30 m one way, within 3% voltage drop, needs 6 mm² copper wire.

AWG and mm²

Area

5.26 mm²

diameter 2.59 mm

Gauge
10 AWG
Diameter
2.588 mm
Diameter in inches
0.1019 in
Area
5.261 mm²
Copper resistance at 20 °C
3.27 ohm per km
Next metric size at or above
6 mm²

10 AWG wire has a cross-section of 5.26 mm².

Wire Size Calculator by Ivorytool, free tools that run in your browser.