Hazen-Williams Calculator

Head loss and pressure drop for water in a pipe, or the flow rate or smallest diameter for a pressure drop you can accept, with the velocity.

L/s or m³/h

In the unit chosen above.

mm

The inside, not the outside.

m

Straight pipe. Add an equivalent length for fittings and valves.

Typical published values for new pipe. Older pipe has a lower C.

Head loss in the pipe

1.46 m

14.32 kPa (0.1432 bar)

Head loss
1.46 m (4.791 ft) of water
Pressure drop
14.32 kPa, 0.1432 bar, 2.077 psi
Pressure drop per 100 m
14.32 kPa (0.1432 bar)
Flow
10 L/s, 36 m³/h, 158.5 gpm
Inside diameter
100 mm (3.937 in)
Velocity
1.27 m/s (4.18 ft/s)
Velocity check
Within about 2 m/s (6.6 ft/s), the usual design guideline.
C factor used
150

10 L/s through 100 m of pipe, 100 mm inside, with C = 150, loses 1.46 m of head (14.32 kPa).

Add this calculator to your website

Free to use on any site or blog. Paste this code where you want the calculator to appear. It stays up to date, needs no account, and keeps your visitors' numbers in their own browser.

Preview

How it works

Water loses pressure to friction as it moves through a pipe. The Hazen-Williams equation estimates that loss for water in a full, round pipe from four things: the flow, the inside diameter, the length and a roughness number called the C factor. A higher C means a smoother pipe and less loss.

Pick what you want to find. Head loss and pressure drop needs the flow, diameter and length. Flow rate needs the diameter, the length and the pressure drop you can accept. Minimum pipe diameter needs the flow, the length and the pressure drop you can accept, and also shows the next Schedule 40 size up so you can pick a real pipe.

The C factors in the list are typical published values for new pipe: 150 for PVC and other plastic, 140 to 150 for copper (145 used), 130 for ductile or cast iron, 120 for steel and 100 for old iron. Real pipe ages, scales and gets rougher, so use a lower number if the pipe is old or the water is hard.

Velocity is checked at the same time. A common design guideline keeps water under about 2 m/s (6.6 ft/s). Above that, pipes get noisy, fittings wear faster and pressure surges from closing valves get stronger.

Check it by hand: for 10 L/s (0.01 m³/s) through 100 m of 100 mm pipe with C = 150, the head loss is 10.67 × 100 × 0.01^1.852 ÷ (150^1.852 × 0.1^4.8704). That is 10.67 × 100 × 0.0001977 ÷ (10,718 × 0.00001348) = 0.2109 ÷ 0.1445 = 1.46 m. The pressure drop is 1.46 × 9.80665 = 14.32 kPa. The velocity is 0.01 ÷ (π × 0.1² ÷ 4) = 1.27 m/s, inside the 2 m/s guideline.

h_f = 10.67 × L × Q^1.852 ÷ (C^1.852 × d^4.8704)
h_f head loss (m), L length (m), Q flow (m³/s), d inside diameter (m), C Hazen-Williams factor
Pressure drop (kPa) = head loss (m) × 9.80665
Velocity = Q ÷ (π ÷ 4 × d²)
Source: the Hazen-Williams equation in SI units, as given in standard hydraulics texts and water-supply design manuals (Williams and Hazen, 1920).

Worked example

10 litres per second (0.01 m³/s) through 100 metres of 100 mm inside diameter plastic pipe, C = 150. Head loss = 10.67 × 100 × 0.01^1.852 ÷ (150^1.852 × 0.1^4.8704) = 1.46 m.

That is 14.3 kPa, or 0.143 bar, about 2.08 psi. The velocity is 0.01 ÷ 0.007854 = 1.27 m/s, which is under the 2 m/s guideline. With C = 130 (new cast iron) the same pipe loses 1.90 m.

Good to know

  • Hazen-Williams is an empirical formula for water at ordinary temperatures, roughly 5 to 25 °C (40 to 75 °F), in turbulent flow. It is not suitable for oil, steam, very hot water or very slow flow. It is usually kept for pipes of 50 mm (2 in) or larger and velocities below about 3 m/s (10 ft/s).
  • It gives friction in straight pipe only. Elbows, tees, valves, meters and filters add loss. Add an equivalent length for them, or use a minor-loss table, and add height changes separately: water rising 1 metre costs about 9.8 kPa (1.42 psi).
  • The C factors are typical published values, not guarantees. The right value for an existing pipe depends on its age and condition.
  • The answer is an estimate for design and checking. For a fire system, a pump selection or a public water main, use the method your code requires and have an engineer confirm it.

Questions people ask

What is the Hazen-Williams equation?

It is a formula for the friction loss of water in a pipe: head loss = 10.67 × length × flow^1.852 ÷ (C^1.852 × diameter^4.8704) in SI units. The calculator applies it and also solves it for flow or for diameter.

What C factor should I use?

About 150 for new PVC or plastic, 140 to 150 for new copper, 130 for new ductile or cast iron, 120 for new steel and 100 for old iron. These are typical published values. Choose lower if the pipe is old.

How do I calculate pressure drop in a pipe?

Find the head loss in metres, then multiply by 9.80665 for kilopascals. Divide kilopascals by 6.895 for psi. The calculator does both for you and also gives the loss per 100 metres or 100 feet.

How do I calculate pipe velocity?

Divide the flow by the inside cross-section area of the pipe. For example, 10 L/s (0.01 m³/s) in a 100 mm pipe, whose area is 0.007854 m², is 1.27 m/s. The result also shows the speed in feet per second.

What is a good maximum velocity for water in a pipe?

Many designers keep it under about 2 m/s (6.6 ft/s) to limit noise, wear and water hammer. Some guides allow 3 m/s in large mains, and lower speeds, such as 1.5 m/s, in building services.

Does this include fittings and elevation?

No. It covers friction in straight pipe. Add the equivalent length of fittings and valves, and add the height the water must rise, which is 9.81 kPa per metre (0.433 psi per foot).

What flow does a 100 mm pipe carry at 2 m/s?

The area is π × 0.1² ÷ 4 = 0.007854 m², so the flow is 2 × 0.007854 = 0.0157 m³/s, which is 15.7 L/s.

Part of the guide: Heating, cooling and water calculators: BTU, pipes, tanks, pumps and pools

Formulas and text last checked on 7 October 2026. Everything is calculated in your browser, so nothing you enter is sent or stored. Spotted a mistake? Tell us and we will fix it.