Insulation Calculator

Find insulation thickness for a target R-value, or the R and U-value of a wall or roof. IECC 2021, NEECA based and ECBC 2017 targets, with cost and payback.

Market

Mode

Insulation thickness
13.24 in336.4 mm
R-value
49 h·ft²·°F/BTU8.63 m²·K/W
U-value
0.0204 BTU/h·ft²·°F0.116 W/m²·K
Coverage
1,000 sq ft1,103.6 ft³
Total cost
$ 3,973Material $ 2,384
Installation $ 1,589
Compliance · IECC 2021
Below the IECC 2021 range minimum (R-60)

Layer diagram

InsideOutside1
  • 1 Fiberglass batt · 13.24 in · R 49
  • R-value 49 h·ft²·°F/BTU · U-value 0.0204 BTU/h·ft²·°F

A steady-state estimate for planning. Prices, degree-days and energy costs are rough placeholders, so replace them with your quote and tariff. Follow your local code and installer.

Step by step working

The calculation with your numbers.

  1. Target R = 49 h·ft²·°F/BTU
  2. R per inch = 3.7
  3. Thickness = 49 ÷ 3.7 = 13.24 in
  4. U-value = 1 ÷ 49 = 0.0204 BTU/h·ft²·°F
  5. Material: 1,000 sq ft × 13.24 in = 1,103.6 ft³
  6. Cost = 1,000 sq ft × $ 3.97 = $ 3,973

Free API and embed

A GET request returns thickness, quantity, U-value, cost and compliance as JSON. No key. Please link back to this page.

https://ivorytool.com/api/insulation?market=us&mode=thick&zone=5&application=attic&material=batt&target=49&area=1000
https://ivorytool.com/api/insulation?market=pk&mode=thick&zone=A&application=roof&material=xps&target=2.5&area=100
https://ivorytool.com/api/insulation?market=in&mode=assembly&application=wall&layers=brick:230,xps:50,plaster:12
<iframe src="https://ivorytool.com/embed/insulation-calculator" width="100%" height="2400" loading="lazy" title="Insulation calculator"></iframe>
Add this calculator to your website

Free to use on any site or blog. Paste this code where you want the calculator to appear. It stays up to date, needs no account, and keeps your visitors' numbers in their own browser.

Preview

Why use our Insulation Calculator?

  • Three markets, treated equally The United States (IECC 2021, R-value, inches), Pakistan (NEECA based targets, RSI, mm) and India (ECBC 2017 U-value limits). Each has its own zones, units and terms. The language is a separate choice.
  • R-value, U-value and layers Work from a target R to a thickness, from a thickness to R, or build a wall or roof layer by layer and get the total R, the U-value and a code check.
  • Nine materials side by side Fiberglass, blown fiberglass, cellulose, open and closed cell spray foam, XPS, EPS, PUF and mineral wool at the same R, with fire, moisture, pros and cons.
  • Cost and payback Material and installation cost, yearly energy saving and the years to pay back. The prices are editable placeholders.
  • A visual layer diagram A cross-section drawn to scale, inside to outside, updating as you type, with a condensation check.
  • Free API and embed A JSON endpoint with no key and an iframe widget with the same market selector.
  • Three languages, no ads English, Hindi and Urdu (right to left). Everything runs in your browser.

How to use the Insulation Calculator

Pick your market and a mode. R to thickness starts from a target R-value, Thickness to R starts from the thickness you have, U-value assembly stacks layers, Compare shows nine materials, and Cost adds payback. Choose a place to set the climate zone, then the application.

For a target, choose the code minimum for your zone, a higher level, or type your own. Pick the material, or enter your own R per inch or conductivity. Add an area to get the volume, boards and cost. Results update as you type.

In assembly mode, list the layers from inside to outside, for example brick, XPS and plaster. Leave the conductivity blank for a typical value. The total includes the inside and outside air films, and you get the U-value, a code check and a condensation check.

To check by hand, take a US attic at R-49 with fiberglass batt at R-3.7 per inch: 49 ÷ 3.7 = 13.24 inches, and the U-value is 1 ÷ 49 = 0.0204. In metric, thickness is the target RSI times the conductivity.

US: R = thickness (in) × R per inch, so thickness = R ÷ R per inch
Metric: R = thickness (m) ÷ λ (W/m·K), so thickness = R × λ
U-value = 1 ÷ R total, and layer R values add up
Films: 0.68 + 0.17 (US) or 0.12 + 0.04 m²·K/W (metric)
RSI = R × 0.1761, R = RSI × 5.678

Worked examples

United States, attic, zone 5, target R-49, fiberglass batt at R-3.7 per inch: thickness 49 ÷ 3.7 = 13.24 inches (336 mm). U-value 1 ÷ 49 = 0.0204 BTU/h·ft²·°F. For 1,000 sq ft that is 1,103.6 ft³ of batt. At the placeholder price of $0.30 per sq ft per inch the cost is about $3,973.

Pakistan, roof, zone A, target RSI 2.5, XPS with λ 0.029 W/m·K: thickness 2.5 × 0.029 = 0.0725 m, or 72.5 mm. U-value 1 ÷ 2.5 = 0.4 W/m²·K. For 100 m² that is 7.25 m³, or 35 boards of 1.2 × 2.4 m.

India, wall, composite zone: 230 mm brick (λ 0.81) gives 0.284, 50 mm XPS gives 1.724, 12 mm plaster (λ 0.72) gives 0.017, and the films add 0.12 + 0.04 = 0.16 m²·K/W. Total R 2.185, so U = 1 ÷ 2.185 = 0.458 W/m²·K. That is at or under the ECBC wall limit of 0.63, so it passes.

Good to know

  • This is a steady-state estimate. Real walls and roofs also have framing, thermal bridges, air leaks and moisture, which lower the performance of the insulation.
  • R per inch and conductivity values are typical figures and vary by product, density and age. Use the value on your product label when you have it.
  • The zone ranges are typical figures for IECC 2021 style tables, NEECA based guidance and ECBC 2017. Your local code and county, state or district rules decide what is required.
  • Prices, degree-days and energy costs are rough placeholders, not quotes. Replace them with your own, and read the payback as a rough guide.

Questions people ask

How much insulation do I need, and what R-value for my attic?

It depends on the climate zone. The IECC 2021 minimums used here are R-30 in zone 1, R-49 in zones 2 and 3, and R-60 in zones 4 to 8. Pick your state to set the zone. The calculator then turns the R-value into a thickness for your material.

How do I convert R-value to RSI?

Multiply the US R-value by 0.1761 to get RSI in m²·K/W, so R-20 is about RSI 3.5. To go back, multiply RSI by 5.678. The calculator shows both together.

What is the difference between R-value and U-value?

R-value measures resistance to heat flow, and a higher number is better. U-value is heat loss, the inverse of R, and a lower number is better. An R of 2.5 m²·K/W is a U-value of 0.4 W/m²·K.

What U-value does ECBC 2017 allow for a roof or wall?

The limits used here are 0.33 W/m²·K for a roof and 0.63 W/m²·K for a wall. Add your layers in assembly mode, with the air films, and the tool shows a pass or a fail.

How thick should roof insulation be in Pakistan?

For a target of RSI 2.5, XPS needs about 72.5 mm, EPS about 90 mm and PUF about 60 mm. The target range used is RSI 2.5 to 3.5 for a roof and 1.5 to 2.5 for a wall.

Is my data saved or uploaded?

No. All the maths happens in your browser and nothing is sent to a server. The link button only copies a web address with your inputs in it.

R-Value Chart by Climate Zone

United States, as used here (the IECC 2021 minimum first, then a higher target): zone 1 attic R-30 to R-38, wall R-13, floor R-13. Zone 2 attic R-49 to R-60, wall R-13 to R-16, floor R-13 to R-19. Zone 3 attic R-49 to R-60, wall R-20 to R-21, floor R-19 to R-25.

Zones 4 to 8 attic R-60 and wall R-30. Floor R-19 to R-25 in zone 4, R-30 in zones 5 and 6, R-38 in zones 7 and 8. Basement walls R-13 in zones 1 to 4 and R-19 in zones 5 to 8.

Pakistan, in RSI: roof 2.5 to 3.5 m²·K/W (about R-14 to R-20) and external wall 1.5 to 2.5 (about R-8.5 to R-14). India, ECBC 2017: roof U up to 0.33, which is R 3.03, and wall U up to 0.63, which is R 1.59.

R-Value vs U-Value: What's the Difference?

R-value is how well a layer resists heat. Layers in series add: R total = R1 + R2 + R3. U-value is how much heat passes, 1 ÷ R total, in BTU/h·ft²·°F or W/m²·K. High R and low U both mean better insulation.

For a whole wall or roof, add the inside and outside air films. They are about R 0.68 and 0.17 in US units, and 0.12 and 0.04 m²·K/W in metric. Test labs measure R per ASTM C518 at a mean temperature of 75°F.

How to Choose the Right Insulation Material

Typical R per inch: fiberglass batt 3.1 to 4.3, blown fiberglass 2.2 to 2.7, cellulose 3.1 to 3.8, open-cell spray foam 3.6 to 3.9, closed-cell spray foam 6.0 to 6.5, XPS about 5.0, mineral wool 3.1 to 4.3.

Choose batts or blown fill when space is generous and the budget is tight. Choose closed-cell foam, XPS or PUF when space is short or moisture is a risk, and cover foam for fire. Mineral wool will not burn.

ECBC Compliance for Insulation

ECBC 2017 sets prescriptive U-value limits for roofs and walls by climate zone: hot-dry, warm-humid, composite, temperate and cold. The limits used here are 0.33 for roofs and 0.63 W/m²·K for walls.

Compliance is on the whole assembly, not the insulation alone, so the total R includes the films. Build the wall in assembly mode and read the pass or fail line.

NEECA Insulation Guidelines

Pakistan's National Energy Efficiency and Conservation Authority (NEECA) promotes insulated roofs and walls. The ranges used here are RSI 2.5 to 3.5 for roofs and 1.5 to 2.5 for walls, as typical targets, with zones A hot-dry, B hot-humid and C cold.

Roofs take most of the summer heat in Karachi, Multan and Lahore, so start there. XPS, EPS, PUF and fiberglass are the usual choices, and a mineral wool or PUF panel suits cold zones such as Quetta and Murree.

Part of the guide: Building material calculators: concrete, blocks, bricks, flooring and more

Formulas and text last checked on 20 November 2026. Everything is calculated in your browser, so nothing you enter is sent or stored. Spotted a mistake? Tell us and we will fix it.