Motor Current Calculator

Estimate motor full-load amps from hp or kW, voltage, phase, efficiency and power factor, with a typical starting current multiple.

kW

The shaft (output) power on the nameplate.

V

For three phase, the voltage between two lines, for example 400, 415, 460 or 480.

%

On the nameplate or data sheet. Typical: 75 to 85% for small motors, 90 to 95% for large ones.

On the nameplate. Typical full-load values are 0.8 to 0.9 for three-phase induction motors, 0.6 to 0.8 for small single-phase motors.

Full-load current, estimate

14.15 A

three-phase motor, 400 V, efficiency 90%, power factor 0.85

Shaft power
7.5 kW
Electrical input power
8.333 kW
Apparent power
9.804 kVA
Starting current, typical (not a calculated value)
84.9 to 99.06 A (6 to 7 times)
Note
Estimate only. The nameplate and the code tables (for example NEC Article 430, Tables 430.248 and 430.250) set the breaker, overload and cable sizes, and a licensed electrician must confirm them.

A 7.5 kW three-phase motor at 400 V, 90% efficiency and power factor 0.85 draws about 14.15 A at full load. Estimate only: check the nameplate.

Add this calculator to your website

Free to use on any site or blog. Paste this code where you want the calculator to appear. It stays up to date, needs no account, and keeps your visitors' numbers in their own browser.

Preview

The same motor on other three-phase voltages

The same motor on other three-phase voltages
VoltageFull-load current
208 V27.21 A
230 V24.61 A
380 V14.9 A
400 V14.15 A
415 V13.64 A
460 V12.3 A
480 V11.79 A

How it works

A motor rating in hp or kW is the mechanical power at the shaft. The supply must deliver more than that, because the motor is not 100 percent efficient, and it must carry current that does no useful work, which is what power factor describes. So the electrical input power is the shaft power divided by the efficiency, and the current follows from the supply voltage. For a three-phase motor the current in each line is the input power divided by 1.732 × line voltage × power factor. For a single-phase motor it is the input power divided by voltage × power factor.

The result is the full-load current, the current at rated output. A motor running below its rating draws less. At start-up an induction motor draws a much larger current for a moment, which is why the tool can show a typical starting multiple. Direct-on-line starting is usually quoted at 6 to 7 times full-load current. Star-delta, soft starters and drives reduce it. These are typical ranges, not a calculation. The real figure is set by the motor design and appears on the nameplate as a locked-rotor code or ratio.

The table under the answer shows the same motor on other common voltages. A motor on a lower voltage draws proportionally more current for the same power. Use the watts to amps calculator for loads that are not motors, and the wire size calculator once the current is known.

Check it by hand: a 7.5 kW motor at 90% efficiency draws 7.5 ÷ 0.9 = 8.333 kW from the supply. With a power factor of 0.85 the apparent power is 8.333 ÷ 0.85 = 9.804 kVA. On three phase at 400 V the current is 9,804 ÷ (1.732 × 400) = 14.15 A. A direct-on-line start of 6 to 7 times that is about 85 to 99 A.

Three phase: I = P ÷ (1.732 × V × efficiency × PF)
Single phase: I = P ÷ (V × efficiency × PF)
P = shaft power in watts (1 hp = 745.7 W, 1 kW = 1,000 W), V = supply voltage (line to line for three phase), efficiency and PF as decimals.
Sources: the standard AC power relations (IEEE Std 1459); hp to watts from NIST SP 811. Code sizing uses the NEC 430.248 and 430.250 full-load current tables, not this formula.

Worked example

A 7.5 kW three-phase motor on 400 V with 90% efficiency and a power factor of 0.85: input power = 7,500 ÷ 0.9 = 8,333 W, and current = 7,500 ÷ (1.732 × 400 × 0.9 × 0.85) = 14.15 A. A direct-on-line start would typically draw 6 to 7 times that, about 85 to 99 A, for a moment.

The same motor as 10 hp at 460 V gives 12.2 A with these efficiency and power factor values. The NEC table value for a 10 hp, 460 V three-phase motor is 14 A, higher because the table is a conservative figure used for sizing and not for your motor in particular.

Good to know

  • This is an estimate. Efficiency and power factor change with load, motor design and age, and the nameplate current is the number that counts for the installed motor.
  • Breaker, overload relay, contactor and cable sizes are set by the code for your country (in the US NEC Article 430, using the table values and margins), the nameplate and a licensed electrician. Do not size protection from this result.
  • The starting current multiples are typical ranges. A high-efficiency motor, a high-inertia load or a weak supply can start differently. For exact values use the locked-rotor data of the motor.
  • The tool assumes a balanced three-phase supply and a motor that is running at its rated output. It does not cover DC motors, motors on variable frequency drives (the line current differs from the motor current) or power-factor-corrected circuits.

Questions people ask

How do you calculate the full load current of a three-phase motor?

Divide the shaft power in watts by 1.732 × line voltage × efficiency × power factor. A 7.5 kW motor on 400 V at 90% efficiency and 0.85 power factor draws about 14.15 A.

How do you calculate single-phase motor amps?

Divide the shaft power in watts by voltage × efficiency × power factor. A 1 hp (746 W) single-phase motor on 230 V at 75% efficiency and 0.7 power factor draws about 6.2 A. Small single-phase motors often have a lower power factor and efficiency than three-phase ones, so use the nameplate values.

How many amps does a 5 hp motor draw?

On 400 V three phase at 90% efficiency and a 0.85 power factor, about 7.0 A. On 230 V single phase at 75% efficiency and a 0.7 power factor it is far higher, about 31 A. The calculator gives the figure for your own voltage and phase.

What is the starting current of a motor?

A direct-on-line induction motor typically draws about 6 to 7 times its full-load current for a moment while it accelerates. Star-delta starters cut it to roughly a third, soft starters and drives reduce it further. The nameplate locked-rotor code gives the real value.

Why is the NEC table current higher than my calculation?

The NEC tables for motor full-load current are standard values used to size conductors and switches, so they do not depend on the exact motor. They are generally higher than a modern efficient motor draws. For overload protection the nameplate current is used.

Can I use this to pick a breaker or cable?

No. It gives an estimate of the running current. Breakers, overloads and cables are sized from the code tables, the nameplate, the starting method and the installation conditions, and an electrician must confirm them. The wire size calculator gives a general idea only.

How do I convert hp to amps?

Convert hp to watts (1 hp = 745.7 W), then divide by the voltage, efficiency and power factor, and by 1.732 for three phase. The calculator does all of it when you choose hp as the rating.

How many amps does a 7.5 kW motor draw at 400 V?

About 14.15 A on three phase, at 90% efficiency and 0.85 power factor. The nameplate current of your motor is the figure to use for protection.

Part of the guide: Electrical, power and solar calculators: amps, wire size, generators and batteries

Formulas and text last checked on 7 October 2026. Everything is calculated in your browser, so nothing you enter is sent or stored. Spotted a mistake? Tell us and we will fix it.