Motor Current Calculator

kW

The shaft (output) power on the nameplate.

V

For three phase, the voltage between two lines, for example 400, 415, 460 or 480.

%

On the nameplate or data sheet. Typical: 75 to 85% for small motors, 90 to 95% for large ones.

On the nameplate. Typical full-load values are 0.8 to 0.9 for three-phase induction motors, 0.6 to 0.8 for small single-phase motors.

Full-load current, estimate

14.15 A

three-phase motor, 400 V, efficiency 90%, power factor 0.85

Shaft power
7.5 kW
Electrical input power
8.333 kW
Apparent power
9.804 kVA
Starting current, typical (not a calculated value)
84.9 to 99.06 A (6 to 7 times)
Note
Estimate only. The nameplate and the code tables (for example NEC Article 430, Tables 430.248 and 430.250) set the breaker, overload and cable sizes, and a licensed electrician must confirm them.

A 7.5 kW three-phase motor at 400 V, 90% efficiency and power factor 0.85 draws about 14.15 A at full load. Estimate only: check the nameplate.