The shaft (output) power on the nameplate.
Mechanical hp, 745.7 W each. The shaft (output) power on the nameplate.
For three phase, the voltage between two lines, for example 400, 415, 460 or 480.
On the nameplate or data sheet. Typical: 75 to 85% for small motors, 90 to 95% for large ones.
On the nameplate. Typical full-load values are 0.8 to 0.9 for three-phase induction motors, 0.6 to 0.8 for small single-phase motors.
Full-load current, estimate
14.15 A
three-phase motor, 400 V, efficiency 90%, power factor 0.85
A 7.5 kW three-phase motor at 400 V, 90% efficiency and power factor 0.85 draws about 14.15 A at full load. Estimate only: check the nameplate.
Motor Current Calculator by Ivorytool, free tools that run in your browser.