Generator Size Calculator

W

Add up the running watts of every appliance that will be on at the same time, including the largest motor.

W

The one with the biggest starting surge, such as the pump or air conditioner. It is already in the total above. Blank for none.

Typical starting multipliers. The label or maker figure is better when you have it.

Generator sets are normally rated at 0.8 for kVA. It only changes the kVA figures.

x

Many portable generators can briefly give about 10 to 30% above the running rating. Use the starting watts on its datasheet.

ft

Rule of thumb: about 3.5% less output per 1,000 ft above 500 ft. The maker's derate chart wins.

%

Take it from the maker's chart for your hottest day. Blank for none.

L per hour

From the maker's data at your load, not a guess. Blank to skip the fuel estimate.

h

Used for the fuel estimate only.

Generator size

5 kW

needs at least 4.17 kW rated, estimate

Running load
3 kW, 3.75 kVA
Starting load (peak)
5 kW, 6.25 kVA
Rated kW needed
4.17 kW
That size in kVA at power factor 0.8
6.3 kVA
Share of its rating used by the running load
60%

Running 3,000 W with a 1,000 W motor starting at 3x needs a generator of at least 4.17 kW, so choose 5 kW.

Generator Size Calculator by Ivorytool, free tools that run in your browser.