Add up the running watts of every appliance that will be on at the same time, including the largest motor.
The one with the biggest starting surge, such as the pump or air conditioner. It is already in the total above. Blank for none.
Typical starting multipliers. The label or maker figure is better when you have it.
Generator sets are normally rated at 0.8 for kVA. It only changes the kVA figures.
Many portable generators can briefly give about 10 to 30% above the running rating. Use the starting watts on its datasheet.
Rule of thumb: about 3.5% less output per 1,000 ft above 500 ft. The maker's derate chart wins.
Rule of thumb: about 3.5% less output per 305 m above 152 m. The maker's derate chart wins.
Take it from the maker's chart for your hottest day. Blank for none.
From the maker's data at your load, not a guess. Blank to skip the fuel estimate.
Used for the fuel estimate only.
Generator size
5 kW
needs at least 4.17 kW rated, estimate
Running 3,000 W with a 1,000 W motor starting at 3x needs a generator of at least 4.17 kW, so choose 5 kW.